Docs
Contents

Access capacity for generation — transmission grid

What it is

The transmission grid seen from the evacuation side, and the headline is that it is essentially full: 225,600 MW taken against 1,416 MW available for power park modules (CAP_DISPONIBLE_MPE) at 43 of the 937 nodes, and 3,562 MW for synchronous modules (CAP_DISPONIBLE_MGES) at 54. That distinction drives the reading: MPE is the power park module — non-synchronous, power-electronics connection, i.e. solar PV and wind — and MGES the synchronous generating module, per Regulation (EU) 2016/631 and Spanish RD 647/2020. A renewables developer looks at MPE, and MPE is the small number. Single operator, REE (R1-000), 787 substations, 220 kV (566), 400 kV (218) and 66 kV (129) in the island systems. What is left concentrates in the Balearic Islands (894 MW across 10 nodes) and Burgos (621 MW across 6). POSICIONES_LIBRES counts physical bays, not MW: 372 free against 494 occupied, and with no free bay there is no connection however many MW are listed. ⚠ In this extract CAP_ALM_DISPONIBLE_MPE equals CAP_DISPONIBLE_MPE in 100 % of rows: storage capacity is not an independent figure here. ⚠ CAP_COMPROMETIDA (394) and NUDO_LIMITADO_SCC (421) are 0/1 flags, and NUDO_AFECCION_RDT is text carrying the name of the constraining node. ⚠ CAP_ADMITIDA_NO_RESUELTA totals 47,331 MW of unresolved applications, almost thirty times the free capacity. Extract PERIODO = 062026, overwritten monthly with no archive. ⚠ CNMC warns the figures are indicative and not directly additive.

According to the publishing agency

Official text, in Spanish, exactly as the upstream service publishes it:

Información de acceso y conexión a las redes En cumplimiento de la Circular informativa 6/2025, de la CNMC los gestores de red envían de forma sistemática información relevante sobre acceso y conexión a las redes de transporte y distribución de electricidad. Tras recopilar y tratar los datos recibidos, la CNMC publica mensualmente la información sobre capacidad de acceso en los mapas correspondientes. Dichas capacidades deben considerarse como informativas y, debido a la influencia de unos nudos sobre otros, sus valores no pueden computarse como directamente sumables. Cabe señalar que las eventuales solicitudes de permisos de acceso y conexión deben dirigirse al gestor de red correspondiente, tal como se indica en la legislación específica sobre acceso y conexión a las redes de electricidad.

At a glance

IDes_energia_capacidad_generacion_transporte
Records937
Size0.1 MB
GeometryPOINT
CRSEPSG:4326
Versionv/2026-08
Sourcecnmc
Upstream layercnmc:Generacion_en_Transporte/0
LicenceCC-BY-SA-4.0

Extent: -17.915957, 27.764805 → 4.257851, 43.693308

Download

curl -H "x-api-key: $GEOVIS_API_KEY" \
https://datos.geovis.es/v1/data/datasets/es_energia_capacidad_generacion_transporte/download

sha256 of this version:

c77f6bf6e94f0862afc527e5ef9f8a7906665f087364806dd9964f8f2786c3fa

Query it without downloading it

import duckdb
con = duckdb.connect(); con.execute("INSTALL spatial; LOAD spatial; INSTALL httpfs; LOAD httpfs;")
con.execute("SELECT count(*) FROM read_parquet('<url-firmada>')").fetchone()

Columns

Column names are kept exactly as the agency publishes them. They are not translated: renaming them would break traceability against the official source.

The literals below are the ones present in the data: they work as-is in a WHERE. Only columns with few distinct values are enumerated; for the rest, the count is given.

ColumnTypeFilledDistinctValues
GESTOR_REDVARCHAR100 %1R1-000
DESCRIPCIONVARCHAR100 %1[REE] RED ELÉCTRICA DE ESP
PROVINCIAVARCHAR100 %50
MUNICIPIOVARCHAR100 %565
SUBESTACIONVARCHAR100 %787
NIVEL_TENSIONINTEGER100 %5220 · 400 · 66 · 132 · 30
CAP_DISPONIBLE_MPEDOUBLE100 %41Range: 0.0 → 152.34
CAP_DISPONIBLE_MGESDOUBLE100 %52Range: 0.0 → 325.3
CAP_ALM_DISPONIBLE_MPEDOUBLE100 %41Range: 0.0 → 152.34
CAP_ALM_DISPONIBLE_MGESINTEGER100 %41Range: 0 → 325
CAP_COMPROMETIDAINTEGER100 %20 · 1
CAP_OCUPADADOUBLE100 %655Range: 0.0 → 2838.3
CAP_ADMITIDA_NO_RESUELTADOUBLE100 %235Range: 0.0 → 1418.12
POSICIONES_OCUPADASINTEGER100 %120 · 1 · 2 · 3 · 4 · 5 · 6 · 9
POSICIONES_LIBRESINTEGER100 %70 · 1 · 2 · 3 · 5 · 4 · 6
NUDO_AFECCION_RDTVARCHAR100 %937
NUDO_LIMITADO_SCCINTEGER100 %20 · 1
PERIODOVARCHAR100 %1062026
prov_codeVARCHAR100 %50
prov_nameVARCHAR100 %50
prov_aproxBOOLEAN100 %1false
_fuenteVARCHAR100 %1cnmc
_fecha_capturaDATE100 %12026-08-22
_fecha_edicionDATE100 %12026-08-22
_licenciaVARCHAR100 %1CC-BY-SA-4.0
_atribucionVARCHAR100 %1Origen de los datos: Comis
bboxSTRUCT(xmin DOUBLE, ymin DOUBLE, xmax DOUBLE, ymax DOUBLE)100 %—
geometryGEOMETRY(‘EPSG:4326’)100 %—